Daikin McQuay Vision™ Indoor Air Handler 900 to 129,000 cfm
- Overview
- Specifications
- Downloads
- Video
VisionTM Air Handlers for High Static Pressure,
Low Leakage Applications
Fan Options

Energy Recovery and Configuration Options... and Much More!
In addition to selectable fan options, Vision also provides multiple energy recovery options and configurations to give your system the best possible fit for your application. Options like fixed plate heat exchangers and energy recovery wheel selections can help increase unit efficiency and can be incorporated into stacked and side-by-side arrangements to minimize footprint.
For information on the Daikin McQuay Vision air handling system, orfor information on our full line of product offerings, visit: www.DaikinMcQuay.com
| Data | Unit Size | |||||
| 003 | 004 | 006 | 008 | 010 | 012 | |
| Airflow range, cfm | 900– 2500 | 1200– 3100 | 1700– 4600 | 2200– 6000 | 2900– 7700 | 3600– 9700 |
| cfm @ 500 ft/min through large face area coil | 1550 | 1950 | 2850 | 3750 | 4800 | 6050 |
| Height × width, inches | 26 × 38 | 30 × 40 | 30 × 52 | 34 × 58 | 36 × 64 | 42 × 66 |
| Cooling coil face area, sq ft | ||||||
| Extended/staggered large | 3.9 | 4.8 | 6.6 | 8.5 | 10.7 | 13.5 |
| Large | 3.1 | 3.9 | 5.7 | 7.5 | 9.6 | 12.1 |
| Extended/staggered medium | 2.6 | 3.4 | 4.7 | 6.4 | 8.3 | 9.8 |
| Medium | 2.1 | 2.8 | 4.1 | 5.6 | 7.4 | 8.8 |
| Small | N/A | 2.3 | 3.3 | 4.7 | 6.4 | 7.7 |
| Fan section–depth, inches | ||||||
| Largest housed fan & motor avail. w/ top hor. dischg. | 32 | 32 | 36 | 40 | 40 | 46 |
| Largest inline fan and motor available | N/A | N/A | N/A | N/A | N/A | 44 |
| Largest belt drive plenum fan & motor available | N/A | N/A | N/A | N/A | 34 | 42 |
| Largest direct drive plenum fan & motor available | N/A | N/A | N/A | 20 | 20 | 54 |
| Largest twin fan and motor available | N/A | N/A | N/A | 50 | 56 | 56 |
| Largest 1 × 3 fan array and motor available | N/A | N/A | N/A | N/A | N/A | N/A |
| Largest 2 × 2 fan array and motor available | N/A | N/A | N/A | N/A | N/A | N/A |
| Largest 2 × 3 fan array and motor available | N/A | N/A | N/A | N/A | N/A | N/A |
| Mixing box–depth, inches | ||||||
| Mixing box only | 20 | 20 | 20 | 20 | 22 | 24 |
| Mixing box with flat filter | 24 | 24 | 24 | 24 | 26 | 28 |
| Mixing box with angular filter | 42 | 42 | 42 | 42 | 44 | 46 |
| Economizer–depth, inches | ||||||
| 40 | 40 | 40 | 40 | 44 | 48 | |
| Blender–depth, inches | ||||||
| Largest Kees | 18 | 20 | 24 | 26 | 28 | 34 |
| Largest Blender Products IV | 18 | 22 | 26 | 30 | 34 | 38 |
| Side load filter sections–depth, inches | ||||||
| Flat 2" and 4" | 12 | 12 | 12 | 12 | 12 | 12 |
| 2" angular | 32 | 30 | 30 | 30 | 30 | 30 |
| Cartridge (12" deep w/2" pre-filter) | 22 | 22 | 22 | 22 | 22 | 22 |
| Bag (36" w/2" pre-filter) | 42 | 42 | 42 | 42 | 42 | 42 |
| Front load filter sections–depth, inches | ||||||
| Cartridge (12" deep w/2" pre-filter) | 16 | 16 | 16 | 16 | 16 | 16 |
| Bag (36" w/2" pre-filter) | 40 | 40 | 40 | 40 | 40 | 40 |
| Face and bypass–depth, inches | ||||||
| Internal | 12 | 12 | 12 | 12 | 12 | 12 |
| External | 18 | 18 | 18 | 20 | 22 | 24 |
| Coil sections–depth, inches | ||||||
| Heating only (2-row water) | 12 | 12 | 12 | 12 | 12 | 12 |
| Cooling only (4-row water) | 18 | 18 | 18 | 18 | 18 | 18 |
| Cooling only (6-row water) | 24 | 24 | 24 | 24 | 24 | 24 |
| Cooling & reheat (12-row cooling & 1-row heating) | 36 | 36 | 36 | 36 | 36 | 36 |
| Vertical cooling only (6-row water) | 30 | 30 | 30 | 30 | 36 | 36 |
| Multizone coil section–depth, inches | ||||||
| 3-deck horizontal with dampers | N/A | N/A | 40 | 42 | 42 | 52 |
| Access sections–depth, inches | ||||||
| 16" deep | 16 | 16 | 16 | 16 | 16 | 16 |
| 24" deep | 24 | 24 | 24 | 24 | 24 | 24 |
| 30" deep | 30 | 30 | 30 | 30 | 30 | 30 |
| 36" deep | 36 | 36 | 36 | 36 | 36 | 36 |
| 42" deep | 42 | 42 | 42 | 42 | 42 | 42 |
| 48" deep | 48 | 48 | 48 | 48 | 48 | 48 |
| 54" deep | 54 | 54 | 54 | 54 | 54 | 54 |
| Diffuser–depth, inches | ||||||
| With housed fan | 10 | 10 | 10 | 12 | 12 | 16 |
| With inline fan | N/A | N/A | N/A | N/A | N/A | 18 |
| Attenuator–depth, inches | ||||||
| Short | 40 | 40 | 40 | 40 | 40 | 40 |
| Medium | 52 | 52 | 52 | 52 | 52 | 52 |
| Long | 64 | 64 | 64 | 64 | 64 | 64 |
| Supply or return plenum–depth, inches | ||||||
| Top, bottom or end opening | 14 | 16 | 16 | 18 | 20 | 22 |
| * Based on typical industry sizes. Vision air handling units are available in 2 inch increments of height and width to fit the exact space requirements. Front load filter sections include 24" upstream plenum section with tread plate for heavy duty floor liner. | ||||||
| Data | Unit Size | |||||
| 014 | 017 | 021 | 025 | 030 | 035 | |
| Airflow range, cfm | 4200– 11,200 | 5000– 13,500 | 6000– 16,000 | 7300– 19,400 | 8500– 22,500 | 10,000– 26,500 |
| cfm @ 500 ft/min through large face area coil | 7000 | 8400 | 10,050 | 12,150 | 14,150 | 16,700 |
| Height × width, inches | 42 × 74 | 46 × 80 | 46 × 80 | 60 × 86 | 60 × 98 | 66 × 102 |
| Cooling coil face area, sq ft | ||||||
| Extended/staggered large | 15.4 | 18.3 | 21.9 | 27.4 | 31.9 | 37.1 |
| Large | 14.0 | 16.8 | 20.1 | 24.3 | 28.3 | 33.4 |
| Extended/staggered medium | 11.2 | 13.7 | 17.2 | 21.3 | 24.8 | 29.7 |
| Medium | 10.2 | 12.6 | 15.8 | 18.2 | 21.2 | 24.1 |
| Small | 8.9 | 11.2 | 14.4 | 16.7 | 19.5 | 22.3 |
| Fan section–depth, inches | ||||||
| Largest housed fan & motor avail. w/ top hor. dischg. | 46 | 50 | 52 | 58 | 58 | 58 |
| Largest inline fan and motor available | 44 | 50 | 54 | 64 | 64 | 70 |
| Largest belt drive plenum fan & motor available | 42 | 48 | 52 | 56 | 58 | 62 |
| Largest direct drive plenum fan & motor available | 54 | 54 | 54 | 66 | 78 | 84 |
| Largest twin fan and motor available | 58 | 58 | 66 | 66 | 74 | 82 |
| Largest 1 × 3 fan array and motor available | N/A | 40 | 40 | 40 | 40 | 46 |
| Largest 2 × 2 fan array and motor available | N/A | N/A | 40 | 40 | 40 | 46 |
| Largest 2 × 3 fan array and motor available | N/A | N/A | 40 | 40 | 40 | 46 |
| Mixing box–depth, inches | ||||||
| Mixing box only | 24 | 26 | 30 | 32 | 32 | 36 |
| Mixing box with flat filter | 28 | 30 | 34 | 36 | 36 | 40 |
| Mixing box with angular filter | 46 | 48 | 52 | 54 | 54 | 58 |
| Economizer–depth, inches | ||||||
| 48 | 52 | 60 | 64 | 64 | 72 | |
| Blender–depth, inches | ||||||
| Largest Kees | 36 | 38 | 42 | 46 | 48 | 58 |
| Largest Blender Products IV | 40 | 46 | 48 | 52 | 60 | 64 |
| Side load filter sections–depth, inches | ||||||
| Flat 2" and 4" | 12 | 12 | 12 | 12 | 12 | 12 |
| 2" angular | 30 | 30 | 30 | 32 | 32 | 32 |
| Cartridge (12" deep w/2" pre-filter) | 22 | 22 | 22 | 22 | 22 | 22 |
| Bag (36" w/2" pre-filter) | 42 | 42 | 42 | 42 | 42 | 42 |
| Front load filter sections–depth, inches | ||||||
| Cartridge (12" deep w/2" pre-filter) | 16 | 16 | 16 | 16 | 16 | 16 |
| Bag (36" w/2" pre-filter) | 40 | 40 | 40 | 40 | 40 | 40 |
| Face and bypass–depth, inches | ||||||
| Internal | 12 | 12 | 12 | 12 | 12 | 12 |
| External | 24 | 26 | 30 | 32 | 32 | 34 |
| Coil sections–depth, inches | ||||||
| Heating only (2-row water) | 12 | 12 | 12 | 12 | 12 | 12 |
| Cooling only (4-row water) | 18 | 18 | 18 | 18 | 18 | 18 |
| Cooling only (6-row water) | 24 | 24 | 24 | 24 | 24 | 24 |
| Cooling & reheat (12-row cooling & 1-row heating) | 36 | 36 | 36 | 36 | 36 | 36 |
| Vertical cooling only (6-row water) | 36 | 36 | 42 | 48 | 48 | 54 |
| Multizone coil section–depth, inches | ||||||
| 3-deck horizontal with dampers | 52 | 54 | 56 | 60 | 60 | 70 |
| Access sections–depth, inches | ||||||
| 16" deep | 16 | 16 | 16 | 16 | 16 | 16 |
| 24" deep | 24 | 24 | 24 | 24 | 24 | 24 |
| 30" deep | 30 | 30 | 30 | 30 | 30 | 30 |
| 36" deep | 36 | 36 | 36 | 36 | 36 | 36 |
| 42" deep | 42 | 42 | 42 | 42 | 42 | 42 |
| 48" deep | 48 | 48 | 48 | 48 | 48 | 48 |
| 54" deep | 54 | 54 | 54 | 54 | 54 | 54 |
| Diffuser–depth, inches | ||||||
| With housed fan | 16 | 16 | 16 | 24 | 24 | 24 |
| With inline fan | 18 | 18 | 22 | 26 | 26 | 28 |
| Attenuator–depth, inches | ||||||
| Short | 40 | 40 | 40 | 40 | 40 | 40 |
| Medium | 52 | 52 | 52 | 52 | 52 | 52 |
| Long | 64 | 64 | 64 | 64 | 64 | 64 |
| Supply or return plenum–depth, inches | ||||||
| Top, bottom or end opening | 22 | 24 | 28 | 30 | 30 | 32 |
| * Based on typical industry sizes. Vision air handling units are available in 2 inch increments of height and width to fit the exact space requirements. Front load filter sections include 24" upstream plenum section with tread plate for heavy duty floor liner. | ||||||
| Data | Unit Size | |||||
| 040 | 050 | 065 | 080 | 085 | 090 | |
| Airflow range, cfm | 11,500– 31,000 | 15,000– 40,000 | 20,000– 54,000 | 21,500– 57,500 | 23,100– 61,600 | 24,600– 65,600 |
| cfm @ 500 ft/min through large face area coil | 19,300 | 24,500 | 33,300 | 35,900 | 38,450 | 41,000 |
| Height × width, inches | 68 × 116 | 80 × 120 | 92 × 136 | 98 × 136 | 104 × 136 | 110 × 136 |
| Cooling coil face area, sq ft | ||||||
| Extended/staggered large | 42.9 | 58.0 | 76.9 | 82.0 | 87.1 | 92.2 |
| Large | 38.6 | 49.0 | 66.6 | 24.3 | 28.3 | 33.4 |
| Extended/staggered medium | 34.3 | 40.1 | 61.5 | 71.8 | 76.9 | 82.0 |
| Medium | 30.0 | 35.7 | 51.2 | 51.2 | 56.4 | 61.5 |
| Small | 27.9 | 31.2 | 46.1 | 46.1 | 51.2 | 56.4 |
| Fan section–depth, inches | ||||||
| Largest housed fan & motor avail. w/ top hor. dischg. | 70 | 80 | 92 | 92 | 92 | 92 |
| Largest inline fan and motor available | 70 | 90 | 96 | 96 | 96 | 96 |
| Largest belt drive plenum fan & motor available | 62 | 70 | 82 | 82 | 82 | 82 |
| Largest direct drive plenum fan & motor available | 86 | 86 | 86 | N/A | N/A | N/A |
| Largest twin fan and motor available | 82 | 82 | N/A | N/A | N/A | N/A |
| Largest 1 × 3 fan array and motor available | 52 | 52 | 52 | 52 | 52 | 52 |
| Largest 2 × 2 fan array and motor available | 52 | 52 | 58 | 62 | 64 | 64 |
| Largest 2 × 3 fan array and motor available | 52 | 52 | 52 | 52 | 52 | 52 |
| Mixing box–depth, inches | ||||||
| Mixing box only | 36 | 40 | 46 | 50 | 54 | 56 |
| Mixing box with flat filter | 40 | 44 | 50 | 54 | 58 | 60 |
| Mixing box with angular filter | 58 | 62 | 68 | 72 | 76 | 78 |
| Economizer–depth, inches | ||||||
| 72 | 80 | 92 | 100 | 108 | 112 | |
| Blender–depth, inches | ||||||
| Largest Kees | 58 | 68 | 76 | 80 | 84 | 84 |
| Largest Blender Products IV | 70 | 74 | 88 | 88 | 92 | 92 |
| Side load filter sections–depth, inches | ||||||
| Flat 2" and 4" | 12 | 12 | 12 | 12 | 12 | 12 |
| 2" angular | 32 | 32 | 32 | 32 | 32 | 32 |
| Cartridge (12" deep w/2" pre-filter) | 22 | 22 | 22 | 22 | 22 | 22 |
| Bag (36" w/2" pre-filter) | 42 | 42 | 42 | 42 | 42 | 42 |
| Front load filter sections–depth, inches | ||||||
| Cartridge (12" deep w/2" pre-filter) | 16 | 16 | 16 | 16 | 16 | 16 |
| Bag (36" w/2" pre-filter) | 40 | 40 | 40 | 40 | 40 | 40 |
| Face and bypass–depth, inches | ||||||
| Internal | 12 | 12 | 12 | 12 | 12 | 12 |
| External | 38 | 44 | 50 | 54 | 56 | 58 |
| Coil sections–depth, inches | ||||||
| Heating only (2-row water) | 12 | 12 | 12 | 12 | 12 | 12 |
| Cooling only (4-row water) | 18 | 18 | 18 | 18 | 18 | 18 |
| Cooling only (6-row water) | 24 | 24 | 24 | 24 | 24 | 24 |
| Cooling & reheat (12-row cooling & 1-row heating) | 36 | 36 | 36 | 36 | 36 | 36 |
| Vertical cooling only (6-row water) | N/A | N/A | N/A | N/A | N/A | N/A |
| Multizone coil section–depth, inches | ||||||
| 3-deck horizontal with dampers | 70 | 76 | 88 | N/A | N/A | N/A |
| Access sections–depth, inches | ||||||
| 16" deep | 16 | 16 | 16 | 16 | 16 | 16 |
| 24" deep | 24 | 24 | 24 | 24 | 24 | 24 |
| 30" deep | 30 | 30 | 30 | 30 | 30 | 30 |
| 36" deep | 36 | 36 | 36 | 36 | 36 | 36 |
| 42" deep | 42 | 42 | 42 | 42 | 42 | 42 |
| 48" deep | 48 | 48 | 48 | 48 | 48 | 48 |
| 54" deep | 54 | 54 | 54 | 54 | 54 | 54 |
| Diffuser–depth, inches | ||||||
| With housed fan | 30 | 30 | 30 | 30 | 30 | 30 |
| With inline fan | 30 | 36 | 38 | 38 | 38 | 38 |
| Attenuator–depth, inches | ||||||
| Short | 40 | 40 | 40 | 40 | 40 | 40 |
| Medium | 52 | 52 | 52 | 52 | 52 | 52 |
| Long | 64 | 64 | 64 | 64 | 64 | 64 |
| Supply or return plenum–depth, inches | ||||||
| Top, bottom or end opening | 32 | 38 | 42 | 48 | 52 | 54 |
| * Based on typical industry sizes. Vision air handling units are available in 2 inch increments of height and width to fit the exact space requirements. Front load filter sections include 24" upstream plenum section with tread plate for heavy duty floor liner. | ||||||
| Data | Unit Size | ||||
| 107 | 124 | 141 | 160 | 169 | |
| Airflow range, cfm | 29,000– 77,500 | 33,600– 89,500 | 40,300– 107,400 | 45,600– 121,800 | 48,400– 129,000 |
| cfm @ 500 ft/min through large face area coil | 48,500 | 55,900 | 67,100 | 76,200 | 80,600 |
| Height × width, inches | 108 × 168 | 108 × 192 | 122 × 192 | 122 × 216 | 122 × 228 |
| Cooling coil face area, sq ft | |||||
| Extended/staggered large | N/A | N/A | N/A | N/A | |
| Large | 96.88 | 111.9 | 134.25 | 152.25 | 161.25 |
| Extended/staggered medium | N/A | N/A | N/A | N/A | |
| Medium | 77.5 | 89.5 | 96.96 | 109.96 | 116.46 |
| Small | N/A | N/A | N/A | N/A | |
| Fan section–depth, inches | |||||
| Largest housed fan & motor avail. w/ top hor. dischg. | 92 | 92 | 92 | 92 | 92 |
| Largest belt drive plenum fan & motor available | 88 | 88 | 88 | 88 | 88 |
| Largest direct drive plenum fan & motor available | 94 | 94 | 94 | 94 | 94 |
| Largest 1 × 3 fan array and motor available | 58 | 62 | 62 | 64 | 64 |
| Largest 2 × 2 fan array and motor available | 64 | 64 | 64 | 64 | 64 |
| Largest 2 × 3 fan array and motor available | 58 | 62 | 62 | 64 | 64 |
| Mixing box–depth, inches | |||||
| Mixing box only | 64 | 64 | 72 | 72 | 72 |
| Economizer–depth, inches | |||||
| 118 | 118 | 136 | 136 | 136 | |
| Blender–depth, inches | |||||
| Largest Kees | 68 | 72 | 80 | 84 | 84 |
| Largest Blender Products IV | 78 | 86 | 92 | 92 | 92 |
| Side load filter sections–depth, inches | |||||
| Flat 2" and 4" | 22/24 | 22/24 | 22/24 | 22/24 | 22/24 |
| Cartridge (12" deep w/2"/4" pre-filter) | 22/24 | 22/24 | 22/24 | 22/24 | 22/24 |
| Bag (36" w/2"/4" pre-filter) | 44/46 | 44/46 | 44/46 | 44/46 | 44/46 |
| Front load filter sections–depth, inches | |||||
| Cartridge (12" deep w/2" pre-filter) | 20/20 | 20/20 | 20/20 | 20/20 | 20/20 |
| Bag (36" w/2" pre-filter) | 44/44 | 44/44 | 44/44 | 44/44 | 44/44 |
| Face and bypass–depth, inches | |||||
| Internal | 12 | 12 | 12 | 12 | 12 |
| External | 58 | 58 | 64 | 64 | 64 |
| Coil sections–depth, inches | |||||
| Heating only (2-row water) | 12 | 12 | 12 | 12 | 12 |
| Cooling only (4-row water) | 18 | 18 | 18 | 18 | 18 |
| Cooling only (6-row water) | 18 | 18 | 18 | 18 | 18 |
| Cooling & reheat (12-row cooling & 1-row heating) | 24 | 24 | 24 | 24 | 24 |
| Access sections–depth, inches | |||||
| 16" deep | 16 | 16 | 16 | 16 | 16 |
| 24" deep | 24 | 24 | 24 | 24 | 24 |
| 30" deep | 30 | 30 | 30 | 30 | 30 |
| 36" deep | 36 | 36 | 36 | 36 | 36 |
| 42" deep | 42 | 42 | 42 | 42 | 42 |
| 48" deep | 48 | 48 | 48 | 48 | 48 |
| 54" deep | 54 | 54 | 54 | 54 | 54 |
| Diffuser–depth, inches | |||||
| With housed fan | 42 | 46 | 46 | 46 | 46 |
| Attenuator–depth, inches | |||||
| Short | 40 | 40 | 40 | 40 | 40 |
| Medium | 52 | 52 | 52 | 52 | 52 |
| Long | 64 | 64 | 64 | 64 | 64 |
| Supply or return plenum–depth, inches | |||||
| Top, bottom or end opening | 36 | 52 | 60 | 60 | 60 |
| * Based on typical industry sizes. Vision air handling units are available in 2 inch increments of height and width to fit the exact space requirements. Front load filter sections include 24" upstream plenum section with tread plate for heavy duty floor liner. | |||||
Brochures
Unit
A/SP 31-152 Vision Customized Indoor Air Handlers - (1,285KB) (Pub: 2010/08/05)
Models:CAC,CAHELECTRONIC COPY ONLY - Brochure is being updated. Use ASP 31-359 or ASP 31-251.Unit
A/SP 31-183A Destiny Indoor Air Handler - 2 page - (2,720KB) (Pub: 2012/08/13)
Models:CAC,CAH600 to 15,000 cfm. 2 to 30 sq ft coil face area. Vertical and horizontal configurations.Unit
A/SP 31-194 Ultraviolet Lights for Air Handler Products - (1,268KB) (Pub: 2012/11/08)
Models:CAC,CAH,RAH,RCS,RDE,RDS,RDTFor pennies a day, UVGI (Ultraviolet Germicidal Irradiation) can improve IAQ by destroying mold, fungi and bacteria on coil and drain pan surfaces.Unit
A/SP 31-226 Quick Ship Programs for Air Handlers and Coils - (427KB) (Pub: 2006/10/20)
Models:CAC,CAH,E-F5,HI-F5,HI-F8,LAH,OAC,OAHDescribes the quick ship programs available for Vision and Destiny indoor air handlers, Skyline outdoor air handlers, and coils.Unit
A/SP 31-251 Extended-Size Vision Indoor Air Handlers - (894KB) (Pub: 2012/05/01)
Models:CAC,CAHVision indoor air handlers in capacities up to 100,000 cfm with coil face areas up to 160 square feet.Unit
A/SP 31-306 Fan Array for Vision Air Handling Systems - (509KB) (Pub: 2010/05/28)
Models:CAC,CAHA multiple fan array option incorporates an array of smaller fans in place of one large single fan and provides customer benefits such as reduced footprint size, noise, and maintenance.Unit
A/SP 31-307 Optional Energy Recovery Wheels for McQuay Vision Air Handling Systems - (1,232KB) (Pub: 2011/05/06)
Models:CAC,CAHEnergy recovery wheels offer a cost-effective and efficient method of recovering exhaust energy and reducing energy cost while meeting the ventilation requirements of ASHRAE Standard 62.1-1999.Unit
A/SP 31-310 Anti-Microbial Protection Liner for Vision and Skyline Air Handler Units - (587KB) (Pub: 2010/05/28)
Models:CAC,CAH,OAC,OAHAnti-microbial protection effectively inhibits the growth of most common micro-organisms such as, bacteria, yeasts, molds and fungi that cause stains, odors, and degradation of applied coatings.Unit
A/SP 31-311 Fan Array Selection for Vision Air Handler Systems - (1,438KB) (Pub: 2010/05/28)
Models:CAC,CAHSelection instructions allow you to pick the optimum fan array and define the required weights and dimensions.Unit
Seismic Certification for Centrifugal Chillers, ASP 31-329 - (1,544KB) (Pub: 2013/06/13)
Models:AR,AZ,CAC,CAH,OAC,OAH,RAH,RAR,RCS,RDT,RFS,RPR,RPS,TSC,WCC,WDC,WMC,WME,WSC2-page brochure on IBC seismic certification and OSHPD pre-approval of Daikin McQuay Centrifugal Chillers. Also lists the IBC certification for Daikin McQuay air handlers, rooftop units and unit ventilatorsControl
A/SP 31-205: Vision Air Handlers With Digital Ready Controls Simplify System Installation - (817K) (Pub: 2005/04/27)
Models:CAHUse this flyer to guide your customers towards specifying Vision air handlers with Digital Ready controls.Accessory
A/SP 31-234 Gas Phase Filters for Air Handlers and Applied Rooftop Systems - (247KB) (Pub: 2007/04/13)
Models:CAH,OAH,RAH,RAR,RCS,RDE,RDT,RFS,RPE,RPS,TIntegral gas-phase filtration system for our applied rooftop and air handler products that can be specified to meet your customer's requirements.Accessory
A/SP 31-240 Motor Control Options for Vision Indoor and Skyline Outdoor Air Handlers - (167KB) (Pub: 2008/03/31)
Models:CAC,CAH,OAC,OAHDescribes the many choices of disconnects, starters and VFDs offered for Vision and Skyline Air Handlers.
A/SP 31-207 Independent IBC 2009 Seismic Certification for RCS Condensing Units, RoofPak and Air Handlers - (84KB) (Pub: 2009/12/07)
Models:CAH,OAH,RAH,RCS,RDS,RDT,RPSIndependent seismic certifications have been updated to comply with IBC 2009 and current ASCE Chapter 7 requirements. This benefits RCS models 015D thru 140D units, Applied Rooftop models RPS, RDT, RAH, and RDS, as well as Vision and Skyline air handlers.
Case Studies
Indoor Air Handlers - Museum - (506KB) (Pub: 2008/05/21)
Models:CAC,CAHMcQuay indoor air handlers are the solution for preserving architecture at historic Federal Hall and provide a 45% cost-savings over the competition.
Indoor Air Handlers and Centrifugal Chillers - Government Office - (502KB) (Pub: 2007/01/22)
Models:CAC,CAH,WSCMcQuay helps Lewis and Clark Administration Building discover first LEED® Platinum certification for state office buildings.
Indoor and Outdoor Air Handlers/Air-cooled Screw Compressor Chillers - Government/Laboratory - (1,971KB) (Pub: 2006/01/25)
Models:AGS,CAHMcQuay HVAC equipment handles the Arizona heat at new research facility
Vision Customized Air Handler - Government/Institutional - (134K) (Pub: 2001/02/03)
Models:CAC,CAHAir Handlers Contribute Comfort, Cost-Efficiency To Arkansas Capitol
Catalogs
Unit
CAT 550-7 Vision Air Handler - (1,737KB) (Pub: 2011/12/07)
Models:CAC,CAHSizes 003 to 090Unit
CAT 565-2 Vision Air Handler - Extended Sizes - (1,616KB) (Pub: 2011/12/07)
Models:CAC,CAHModels CAC/CAH 107G to 169G, 107 to 169 Tons
Installation and Operation Manuals
Unit
IM 672-9 Vision Indoor Air Handler - (5,688KB) (Pub: 2013/04/24)
Models:CAC,CAHCAC and CAH Sizes 003 to 090Unit
IM 915-2 Vision Air Handler - Extended Sizes - (1,630KB) (Pub: 2011/11/17)
Models:CAC,CAHCAC and CAH Sizes 107 - 169Control
OM 1190-1 Daikin McQuay MD4 VFD - (2,679KB) (Pub: 2013/05/29)
Models:CAC,CAH,DPS,LAH,MPS,OAC,OAH,RAH,RDE,RDS,RDT,RFR,RPE,RPS,SWP,SWTMD4 Variable Frequency Drive Controller for Packaged Rooftop Units: DPS, MPS, RPS, RFS, RDT, RPE, RDE; Rooftop Air Handler Units: RDS, RAH; Indoor Air Handler Units: LAH, CAH; Outdoor Air Handler Units: OAH; Vertical Self-Contained Units: SWP, SWTControl
OM 1191 Daikin McQuay MD5 VFD - (3,042KB) (Pub: 2013/02/13)
Models:CAC,CAH,DPS,LAH,MPS,OAC,OAH,RAH,RDE,RDS,RDT,RFR,RPE,RPS,SWP,SWTMD5 Variable Frequency Drive Controller for Packaged Rooftop Units: DPS, MPS, RPS, RFS, RDT, RPE, RDE; Rooftop Air Handler Units: RDS, RAH; Indoor Air Handler Units: LAH, CAH; Outdoor Air Handler Units: OAH; Vertical Self-Contained Units: SWP, SWTControl
OM 844-5 MD2 Variable Speed Drive Controller - (2,104KB) (Pub: 2011/06/01)
Models:CAC,CAH,LHA,MPS,OAC,OAH,RAH,RDE,RDS,RFS,RPE,RPS,SWP,SWTPackaged Rooftop Units RPS/RFS/RDT/RPE/RDE, Rooftop Air Handler Units RDS/RAH, Indoor and Outdoor Air Handler Units LAH/CAC/CAH/OAC/OAH, Vertical Self-Contained Units SWP/SWT, Commercial Packaged Rooftop Units MPS (15 - 75 ton)Accessory
IM 808-1 Ultraviolet Lights on McQuay Vision Air Handlers - (372KB) (Pub: 2009/11/17)
Models:CAC,CAHModels CAH/CAC
Replacement Parts Lists
  Click here to view the Replacement Parts Model Index
Unit
Replacement Parts List: 7000045 - (2,173KB) (Pub: 2013/03/22)
Models:CAC,CAH,OAC,OAHRPL: CAC, CAH 003-169, Vision Condensing/Air Handler. OAC, OAH, 003-090, Skyline Air Handler, Vintage F,
Revit Templates
Unit
Revit Air Handler Template Training Video - (74MB) (Pub: 2009/06/26)
Models:CAC,CAH,OAHZipped file of a setup program to install the McQuay Revit air handler template training video and support files.Unit
Vision Air Handler Revit 2009 Templates - (13,532K) (Pub: 2009/06/26)
Models:CAC,CAHZipped file of a setup program to install the Revit 2009 air handler templates for McQuay Vision indoor air handler units.
Sales and Engineering Data
Unit
ED 8028 Seismic Certification of Daikin McQuay Centrifugal Chillers - (91KB) (Pub: 2012/06/22)
Models:AE,AR,AV,AZ,CAC,CAH,OAC,OAH,RAH,RDS,RFS,TSC,WCC,WDC,WMC,WME,WSCLists the seismic certification details of Daikin McQuay Centrifugal chillers and other products. Covers both IBC certification and OSHPD pre-approval.
Seismic Certification
Unit
A/SP 31-152 Vision Customized Indoor Air Handlers - (1,285KB) (Pub: 2010/08/05)
Models:CAC,CAHELECTRONIC COPY ONLY - Brochure is being updated. Use ASP 31-359 or ASP 31-251.
A/SP 31-207 Independent IBC 2009 Seismic Certification for RCS Condensing Units, RoofPak and Air Handlers - (84KB) (Pub: 2009/12/07)
Models:CAH,OAH,RAH,RCS,RDS,RDT,RPSIndependent seismic certifications have been updated to comply with IBC 2009 and current ASCE Chapter 7 requirements. This benefits RCS models 015D thru 140D units, Applied Rooftop models RPS, RDT, RAH, and RDS, as well as Vision and Skyline air handlers.
Software
Unit
Vision Air Handler Revit 2010 Templates - (17,738K) (Pub: 2010/05/25)
Models:CAC,CAHZipped file of a setup program to install the Revit 2010 air handler templates for McQuay Vision indoor air handler units.