Daikin McQuay Vision™ Indoor Air Handler 900 to 129,000 cfm
  • Overview
  • Specifications
  • Downloads
  • Video

VisionTM  Air Handlers for High Static Pressure,

Low Leakage Applications

 

Overview
Daikin McQuay strives to provide building owners with the ultimate solution in high static pressure, low leak applications, and our Vision air handler does just that. Vision provides the ability to attain a maximum of Class 6 leakage up to +/-8’’ of internal static per ASHRAE’s 111 Standard, which is well under the industry quality standard of one percent.

Vision unique variable dimensioning of up to 2’’ increments, modular design, and best in class fan performance provides an economical, energy efficient, and out-of-box solution for demanding applications that are commonly encountered when advanced filtration and energy recovery are required.

Designed and engineered for the flexibility and performance you demand, Vision offers a proven, high quality, sustainable design for increasing occupant health and comfort, with industry leading energy efficiencies and lots of options for cost saving solutions.

 

HVAC System Type
Indoor air handler

Building Application
Ideal for applications like healthcare facilities, clean-room and labs that require increased filtration.

Featuring
Low leakage construction with up to +/-8” of internal static pressure, 2” Variable Dimensioning™, modular design, foam injected panels, multiple filter and energy recovery options, stacked and side-by-side configurations, fixed plate heat exchangers, UV lights, sloped drain pan, anti-microbial liner, and much more.
Benefits
Spec high filtration job applications with industry leading energy efficiencies for cost saving solutions!


Fan Options

Energy Recovery and Configuration Options... and Much More!

In addition to selectable fan options, Vision also provides multiple energy recovery options and configurations to give your system the best possible fit for your application. Options like fixed plate heat exchangers and energy recovery wheel selections can help increase unit efficiency and can be incorporated into stacked and side-by-side arrangements to minimize footprint.

For information on the Daikin McQuay Vision air handling system, orfor information on our full line of product offerings, visit: www.DaikinMcQuay.com

 

 
  
DataUnit Size
003004006008010012
Airflow range, cfm900–
2500
1200–
3100
1700–
4600
2200–
6000
2900–
7700
3600–
9700
cfm @ 500 ft/min through large face area coil155019502850375048006050
Height × width, inches26 × 3830 × 4030 × 5234 × 5836 × 6442 × 66
Cooling coil face area, sq ft
Extended/staggered large3.94.86.68.510.713.5
Large3.13.95.77.59.612.1
Extended/staggered medium2.63.44.76.48.39.8
Medium2.12.84.15.67.48.8
SmallN/A2.33.34.76.47.7
Fan section–depth, inches
Largest housed fan & motor avail. w/ top hor. dischg.323236404046
Largest inline fan and motor availableN/AN/AN/AN/AN/A44
Largest belt drive plenum fan & motor availableN/AN/AN/AN/A3442
Largest direct drive plenum fan & motor availableN/AN/AN/A202054
Largest twin fan and motor availableN/AN/AN/A505656
Largest 1 × 3 fan array and motor availableN/AN/AN/AN/AN/AN/A
Largest 2 × 2 fan array and motor availableN/AN/AN/AN/AN/AN/A
Largest 2 × 3 fan array and motor availableN/AN/AN/AN/AN/AN/A
Mixing box–depth, inches
Mixing box only202020202224
Mixing box with flat filter242424242628
Mixing box with angular filter424242424446
Economizer–depth, inches
 404040404448
Blender–depth, inches
Largest Kees182024262834
Largest Blender Products IV182226303438
Side load filter sections–depth, inches
Flat 2" and 4"121212121212
2" angular323030303030
Cartridge (12" deep w/2" pre-filter)222222222222
Bag (36" w/2" pre-filter)424242424242
Front load filter sections–depth, inches
Cartridge (12" deep w/2" pre-filter)161616161616
Bag (36" w/2" pre-filter)404040404040
Face and bypass–depth, inches
Internal121212121212
External181818202224
Coil sections–depth, inches
Heating only (2-row water)121212121212
Cooling only (4-row water)181818181818
Cooling only (6-row water)242424242424
Cooling & reheat (12-row cooling & 1-row heating)363636363636
Vertical cooling only (6-row water)303030303636
Multizone coil section–depth, inches
3-deck horizontal with dampersN/AN/A40424252
Access sections–depth, inches
16" deep161616161616
24" deep242424242424
30" deep303030303030
36" deep363636363636
42" deep424242424242
48" deep484848484848
54" deep545454545454
Diffuser–depth, inches
With housed fan101010121216
With inline fanN/AN/AN/AN/AN/A18
Attenuator–depth, inches
Short404040404040
Medium525252525252
Long646464646464
Supply or return plenum–depth, inches
Top, bottom or end opening141616182022
* Based on typical industry sizes. Vision air handling units are available in 2 inch increments of height and width to fit the exact space requirements.
Front load filter sections include 24" upstream plenum section with tread plate for heavy duty floor liner.

 

DataUnit Size
014017021025030035
Airflow range, cfm4200–
11,200
5000–
13,500
6000–
16,000
7300–
19,400
8500–
22,500
10,000–
26,500
cfm @ 500 ft/min through large face area coil7000840010,05012,15014,15016,700
Height × width, inches42 × 7446 × 8046 × 8060 × 8660 × 9866 × 102
Cooling coil face area, sq ft
Extended/staggered large15.418.321.927.431.937.1
Large14.016.820.124.328.333.4
Extended/staggered medium11.213.717.221.324.829.7
Medium10.212.615.818.221.224.1
Small8.911.214.416.719.522.3
Fan section–depth, inches
Largest housed fan & motor avail. w/ top hor. dischg.465052585858
Largest inline fan and motor available445054646470
Largest belt drive plenum fan & motor available424852565862
Largest direct drive plenum fan & motor available545454667884
Largest twin fan and motor available585866667482
Largest 1 × 3 fan array and motor availableN/A4040404046
Largest 2 × 2 fan array and motor availableN/AN/A40404046
Largest 2 × 3 fan array and motor availableN/AN/A40404046
Mixing box–depth, inches
Mixing box only242630323236
Mixing box with flat filter283034363640
Mixing box with angular filter464852545458
Economizer–depth, inches
 485260646472
Blender–depth, inches
Largest Kees363842464858
Largest Blender Products IV404648526064
Side load filter sections–depth, inches
Flat 2" and 4"121212121212
2" angular303030323232
Cartridge (12" deep w/2" pre-filter)222222222222
Bag (36" w/2" pre-filter)424242424242
Front load filter sections–depth, inches
Cartridge (12" deep w/2" pre-filter)161616161616
Bag (36" w/2" pre-filter)404040404040
Face and bypass–depth, inches
Internal121212121212
External242630323234
Coil sections–depth, inches
Heating only (2-row water)121212121212
Cooling only (4-row water)181818181818
Cooling only (6-row water)242424242424
Cooling & reheat (12-row cooling & 1-row heating)363636363636
Vertical cooling only (6-row water)363642484854
Multizone coil section–depth, inches
3-deck horizontal with dampers525456606070
Access sections–depth, inches
16" deep161616161616
24" deep242424242424
30" deep303030303030
36" deep363636363636
42" deep424242424242
48" deep484848484848
54" deep545454545454
Diffuser–depth, inches
With housed fan161616242424
With inline fan181822262628
Attenuator–depth, inches
Short404040404040
Medium525252525252
Long646464646464
Supply or return plenum–depth, inches
Top, bottom or end opening222428303032
* Based on typical industry sizes. Vision air handling units are available in 2 inch increments of height and width to fit the exact space requirements.
Front load filter sections include 24" upstream plenum section with tread plate for heavy duty floor liner.

 

DataUnit Size
040050065080085090
Airflow range, cfm11,500–
31,000
15,000–
40,000
20,000–
54,000
21,500–
57,500
23,100–
61,600
24,600–
65,600
cfm @ 500 ft/min through large face area coil19,30024,50033,30035,90038,45041,000
Height × width, inches68 × 11680 × 12092 × 13698 × 136104 × 136110 × 136
Cooling coil face area, sq ft
Extended/staggered large42.958.076.982.087.192.2
Large38.649.066.624.328.333.4
Extended/staggered medium34.340.161.571.876.982.0
Medium30.035.751.251.256.461.5
Small27.931.246.146.151.256.4
Fan section–depth, inches
Largest housed fan & motor avail. w/ top hor. dischg.708092929292
Largest inline fan and motor available709096969696
Largest belt drive plenum fan & motor available627082828282
Largest direct drive plenum fan & motor available868686N/AN/AN/A
Largest twin fan and motor available8282N/AN/AN/AN/A
Largest 1 × 3 fan array and motor available525252525252
Largest 2 × 2 fan array and motor available525258626464
Largest 2 × 3 fan array and motor available525252525252
Mixing box–depth, inches
Mixing box only364046505456
Mixing box with flat filter404450545860
Mixing box with angular filter586268727678
Economizer–depth, inches
 728092100108112
Blender–depth, inches
Largest Kees586876808484
Largest Blender Products IV707488889292
Side load filter sections–depth, inches
Flat 2" and 4"121212121212
2" angular323232323232
Cartridge (12" deep w/2" pre-filter)222222222222
Bag (36" w/2" pre-filter)424242424242
Front load filter sections–depth, inches
Cartridge (12" deep w/2" pre-filter)161616161616
Bag (36" w/2" pre-filter)404040404040
Face and bypass–depth, inches
Internal121212121212
External384450545658
Coil sections–depth, inches
Heating only (2-row water)121212121212
Cooling only (4-row water)181818181818
Cooling only (6-row water)242424242424
Cooling & reheat (12-row cooling & 1-row heating)363636363636
Vertical cooling only (6-row water)N/AN/AN/AN/AN/AN/A
Multizone coil section–depth, inches
3-deck horizontal with dampers707688N/AN/AN/A
Access sections–depth, inches
16" deep161616161616
24" deep242424242424
30" deep303030303030
36" deep363636363636
42" deep424242424242
48" deep484848484848
54" deep545454545454
Diffuser–depth, inches
With housed fan303030303030
With inline fan303638383838
Attenuator–depth, inches
Short404040404040
Medium525252525252
Long646464646464
Supply or return plenum–depth, inches
Top, bottom or end opening323842485254
* Based on typical industry sizes. Vision air handling units are available in 2 inch increments of height and width to fit the exact space requirements.
Front load filter sections include 24" upstream plenum section with tread plate for heavy duty floor liner.

 

DataUnit Size
107124141160169
Airflow range, cfm29,000–
77,500
33,600–
89,500
40,300–
107,400
45,600–
121,800
48,400–
129,000
cfm @ 500 ft/min through large face area coil48,50055,90067,10076,20080,600
Height × width, inches108 × 168108 × 192122 × 192122 × 216122 × 228
Cooling coil face area, sq ft
Extended/staggered largeN/AN/AN/AN/A 
Large96.88111.9134.25152.25161.25
Extended/staggered mediumN/AN/AN/AN/A 
Medium77.589.596.96109.96116.46
SmallN/AN/AN/AN/A 
Fan section–depth, inches
Largest housed fan & motor avail. w/ top hor. dischg.9292929292
Largest belt drive plenum fan & motor available8888888888
Largest direct drive plenum fan & motor available9494949494
Largest 1 × 3 fan array and motor available5862626464
Largest 2 × 2 fan array and motor available6464646464
Largest 2 × 3 fan array and motor available5862626464
Mixing box–depth, inches
Mixing box only6464727272
Economizer–depth, inches
 118118136136136
Blender–depth, inches
Largest Kees6872808484
Largest Blender Products IV7886929292
Side load filter sections–depth, inches
Flat 2" and 4"22/2422/2422/2422/2422/24
Cartridge (12" deep w/2"/4" pre-filter)22/2422/2422/2422/2422/24
Bag (36" w/2"/4" pre-filter)44/4644/4644/4644/4644/46
Front load filter sections–depth, inches
Cartridge (12" deep w/2" pre-filter)20/2020/2020/2020/2020/20
Bag (36" w/2" pre-filter)44/4444/4444/4444/4444/44
Face and bypass–depth, inches
Internal1212121212
External5858646464
Coil sections–depth, inches
Heating only (2-row water)1212121212
Cooling only (4-row water)1818181818
Cooling only (6-row water)1818181818
Cooling & reheat (12-row cooling & 1-row heating)2424242424
Access sections–depth, inches
16" deep1616161616
24" deep2424242424
30" deep3030303030
36" deep3636363636
42" deep4242424242
48" deep4848484848
54" deep5454545454
Diffuser–depth, inches
With housed fan4246464646
Attenuator–depth, inches
Short4040404040
Medium5252525252
Long6464646464
Supply or return plenum–depth, inches
Top, bottom or end opening3652606060
* Based on typical industry sizes. Vision air handling units are available in 2 inch increments of height and width to fit the exact space requirements.
Front load filter sections include 24" upstream plenum section with tread plate for heavy duty floor liner.

 

 

 

Brochures
Case Studies
Catalogs
Installation and Operation Manuals
  • Unit  IM 672-9 Vision Indoor Air Handler - (5,688KB) (Pub: 2013/04/24)
     
    Models:CAC,CAH
     
    CAC and CAH Sizes 003 to 090
  • Unit  IM 915-2 Vision Air Handler - Extended Sizes - (1,630KB) (Pub: 2011/11/17)
     
    Models:CAC,CAH
     
    CAC and CAH Sizes 107 - 169
  • Control  OM 1190-1 Daikin McQuay MD4 VFD - (2,679KB) (Pub: 2013/05/29)
     
    Models:CAC,CAH,DPS,LAH,MPS,OAC,OAH,RAH,RDE,RDS,RDT,RFR,RPE,RPS,SWP,SWT
     
    MD4 Variable Frequency Drive Controller for Packaged Rooftop Units: DPS, MPS, RPS, RFS, RDT, RPE, RDE; Rooftop Air Handler Units: RDS, RAH; Indoor Air Handler Units: LAH, CAH; Outdoor Air Handler Units: OAH; Vertical Self-Contained Units: SWP, SWT
  • Control  OM 1191 Daikin McQuay MD5 VFD - (3,042KB) (Pub: 2013/02/13)
     
    Models:CAC,CAH,DPS,LAH,MPS,OAC,OAH,RAH,RDE,RDS,RDT,RFR,RPE,RPS,SWP,SWT
     
    MD5 Variable Frequency Drive Controller for Packaged Rooftop Units: DPS, MPS, RPS, RFS, RDT, RPE, RDE; Rooftop Air Handler Units: RDS, RAH; Indoor Air Handler Units: LAH, CAH; Outdoor Air Handler Units: OAH; Vertical Self-Contained Units: SWP, SWT
  • Control  OM 844-5 MD2 Variable Speed Drive Controller - (2,104KB) (Pub: 2011/06/01)
     
    Models:CAC,CAH,LHA,MPS,OAC,OAH,RAH,RDE,RDS,RFS,RPE,RPS,SWP,SWT
     
    Packaged Rooftop Units RPS/RFS/RDT/RPE/RDE, Rooftop Air Handler Units RDS/RAH, Indoor and Outdoor Air Handler Units LAH/CAC/CAH/OAC/OAH, Vertical Self-Contained Units SWP/SWT, Commercial Packaged Rooftop Units MPS (15 - 75 ton)
  • Accessory  IM 808-1 Ultraviolet Lights on McQuay Vision Air Handlers - (372KB) (Pub: 2009/11/17)
     
    Models:CAC,CAH
     
    Models CAH/CAC
Replacement Parts Lists
   Click here to view the Replacement Parts Model Index
  • Unit  Replacement Parts List: 7000045 - (2,173KB) (Pub: 2013/03/22)
     
    Models:CAC,CAH,OAC,OAH
     
    RPL: CAC, CAH 003-169, Vision Condensing/Air Handler. OAC, OAH, 003-090, Skyline Air Handler, Vintage F,
Revit Templates
  • Unit  Revit Air Handler Template Training Video - (74MB) (Pub: 2009/06/26)
     
    Models:CAC,CAH,OAH
     
    Zipped file of a setup program to install the McQuay Revit air handler template training video and support files.
  • Unit  Vision Air Handler Revit 2009 Templates - (13,532K) (Pub: 2009/06/26)
     
    Models:CAC,CAH
     
    Zipped file of a setup program to install the Revit 2009 air handler templates for McQuay Vision indoor air handler units.
Sales and Engineering Data
Seismic Certification
Software
  • Unit  Vision Air Handler Revit 2010 Templates - (17,738K) (Pub: 2010/05/25)
     
    Models:CAC,CAH
     
    Zipped file of a setup program to install the Revit 2010 air handler templates for McQuay Vision indoor air handler units.